parameter descriptions
vacon
•
83
24-hour s358 (0) 201 212 575 • Email: [email protected]
9
9.9 Protections (Control panel:Menu Par->P13)
13.5 S
TALL
PROTECTION
0 =
No action
1 =
Alarm
2 =
Fault, coast
The motor stall protection protects the motor from short time overload situa-
tions such as one caused by a stalled shaft. The stall current is I
nMotor
*1.3,
stall time 15 seconds and stall frequency limit 25 Hz . If the current is higher
than the limit and output frequency is lower than the limit, the stall state is
true and the drive reacts according to this parameter. There is actually no real
indication of the shaft rotation.
f
I
Inmotor *1.3
25Hz
Stall area
Figure 9.12: Stall characteristics
13.6 U
NDER
LOAD
PROTECTION
0 =
No action
1 =
Alarm
2 =
Fault, coast
The purpose of the motor underload protection is to ensure that there is load
on the motor when the drive is running. If the motor loses its load there might
be a problem in the process, e.g. a broken belt or a dry pump.
The underload protection time limit is 20 seconds, which is the maximum time
allowed for an underload state to exist before causing a trip according to this
parameter.
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...