6.2 Control I/O
Figure 6.1: Vacon 10 I/O
Terminal
Signal
Factory preset
Description
1
+10Vre Ref. voltage out
Maximum load 10 mA
2
AI1
Analog signal in 1
Freq. reference
P)
0 - 10 V Ri = 200 k
(min)
3
GND
I/O signal ground
6
24Vout
24V output for DI's
%, max. load 50 mA
7
GND
I/O signal ground
8
DI1
Digital input 1
Start forward
P)
0 - +30 V Ri = 12 k min
9
DI2
Digital input 2
Start reverse
P)
10 DI3
Digital input 3
Fault reset
P)
A
A
RS485 signal A
FB Communication Negative
B
B
RS485 signal B
FB Communication Positive
4
AI2
Analog signal in 2
PI actual value
P)
0(4) - 20 mA, Ri = 200
5
GND
I/O signal ground
13 GND
I/O signal ground
14 DI4
Digital input 4
Preset speed B0
P)
0 - +30 V Ri = 12 k
(min)
15 DI5
Digital input 5
Preset speed B1
P)
16 DI6
Digital input 6
External fault
P)
18 AO
Analog Output
Output frequency
P)
0(4) - 20 mA, RL = 500
20 DO
Digital signal out
Active = READY
P)
Open collector, max.
load 48V/50mA
22 RO 13
Relay out 1 Active = RUN
P)
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
23 RO 14
24 RO 22
Relay out 2 Active = FAULT
P)
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
25 RO 21
26 RO 24
Table 6.2: Vacon 10 default I/O configuration and connections
P) = Programmable function, see parameter lists and descriptions,
chapters 8 and 9.
20
ON
OFF
mA
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...