parameter descriptions
vacon
•
91
24-hour s358 (0) 201 212 575 • Email: [email protected]
9
9.13 Modbus RTU
Vacon 10 has a built-in Modbus RTU bus interface. The signal level of the interface
is in accordance with the RS-485 standard.
The built-in Modbus connection of Vacon 10 supports the following function codes:
9.13.1 Termination resistor
The RS-485 bus is terminated with termination resistors of 120 ohms in both ends.
Vacon 10 has a built-in termination resistor which is switched off as a default (pre-
sented below). The termination resistor can be switched on and off with the right
hand dip switch located above IO-terminals in the front of the drive (see below).
Figure 9.20: Vacon 10 I/O
9.13.2 Modbus address area
The Modbus interface of Vacon 10 uses the ID numbers of the application parameters
as addresses. The ID numbers can be found in the parameter tables in chapter 8.
When several parameters / monitoring values are read at a time, they must be con-
secutive. 11 addresses can be read and the addresses can be parameters or moni-
toring values.
Function
code
Function name
Address
Broadcast
messages
03
Read Holding Registers
All ID numbers
No
04
Read Input Registers
All ID numbers
No
06
Write Single Registers
All ID numbers
Yes
16
Write multiple registers
All ID numbers
Yes
Table 9.3: Modbus RTU
ON
OFF
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...