9.10 Automatic reset (Control panel: Menu PAR -> P14)
14.1 A
UTOMATIC
RESET
Activate the Automatic reset after fault with this parameter.
NOTE:
Automatic reset is allowed for certain faults only.
Fault:
1
. Under voltage
2
. Over voltage
3
. Over current
4
. Motor temperature
5
. Under load
14.3 T
RIAL
TIME
The Automatic restart function restarts the frequency converter when the
faults have disappeared and the waiting time has elapsed.
The time count starts from the first autoreset. If the number of faults occur-
ring during the trial time exceeds three, the fault state becomes active. Oth-
erwise the fault is cleared after the trial time has elapsed and the next fault
starts the trial time count again. See Figure 9.16.
If a single fault remains during the trial time, a fault state is true.
Fault trigger
Motor stop signal
Motor start signal
Supervis ion
Restart 1
Restart 2
Trial time
par.14.3
Fault active
RESET/
Fault reset
Autoreset function: (Trials = 2)
Wait time
pa r.1 4.2
Wait time
pa r.1 4.2
Wait time
pa r.1 4.2
Figure 9.16: Example of Automatic restarts with two restarts
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...