8.6 Digital inputs (Control panel: Menu PAR -> P5)
8.7 Analogue inputs (Control panel: Menu PAR -> P6)
Code
Parameter
Min
Max
Unit Default
ID
Note
0
6
1
403
0
= Not used
1
= DI1
2
= DI2
3
= DI3
4
= DI4
5
= DI5
6
= DI6
P5.2 I / O control signal 2
0
6
2
404 As parameter 5.1
P5.3
0
6
0
412 As parameter 5.1
P5.4
0
6
6
405 As parameter 5.1
P5.5
0
6
0
406 As parameter 5.1
P5.6
0
6
3
414 As parameter 5.1
P5.7
0
6
0
407 As parameter 5.1
P5.8
0
6
4
419 As parameter 5.1
P5.9
0
6
5
420 As parameter 5.1
P5.10
0
6
0
421 As parameter 5.1
P5.11
0
6
0
408 As parameter 5.1
P5.12
Disable PI
0
6
0
1020 As parameter 5.1
P5.13
Force to I/O
0
6
0
409 As parameter 5.1
Table 8.6: Digital inputs
Code
Parameter
Min
Max
Unit
Default
ID
Note
P6.1
AI1 Signal range
0
1
0
379
0
= 0 - 100% ( 0 - 10 V)
1
= 20% - 100% ( 2 - 10 V)
P6.2
-100,00
100,00
%
0,00
380 0,00 = no min scaling
P6.3
-100,00
300,00
%
100,00
381 100,00 = no max scaling
P6.4
0,0
10,0
s
0,1
378 0 = no filtering
P6.5
AI2 signal range
0
1
0
390
0 = 0 - 100% ( 0 - 20 mA)
1 = 20% - 100% (4 -20
mA)
P6.6
-100,00
100,00
%
0,00
391 0,00 = no min scaling
P6.7
-100,00
300,00
%
100,00
392 100,00 = no max scaling
P6.8
0,0
10,0
s
0,1
389
0
= no filtering
Table 8.7: Analogue inputs
i
i
i
i
i
i
i
i
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...