The drive does not rotate the motor during Standstill identification. When ID
run is ready the drive is stopped. Drive will start normally, when the next start
command is given.
After end the identification, the drive need stop the start command. If control
place is Keypad, user need press stop button. If control place is IO,user need
put DI(Control signal) inactivate. If control place is fieldbus, user need set the
control bit to 0.
The ID run improves the torque calculations and the automatic torque boost
function. It will also result in a better slip compensation in speed control
(more accurate RPM).
The parameters below will change after ID run successfully,
a. P1.9 U / f ratio
b. P1.12 U / f mid point frequency
c. P1.13 U / f mid point voltage
d. P1.14 Zero freq voltage
e. P1.18 Motor identification (1->0)
f. P1.19 Rs voltage drop
Note!
The nameplate data of the motor has to be set BEFORE doing ID run.