installation
vacon
•
27
24-hour support (0)201 212 575 • Email: [email protected]
3
Note!
To fulfil standard EN61800-5-1, the protective co nductor should be
at least
10 mm
2
Cu or 16 mm
2
Al
. Another possibility is to use an additional protective con-
ductor of at least the same size as the original one.
Frame
Type
Fuse
[A]
Mains
cable
Cu
[mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0001-0003
6
3*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI2
0004-0006
10
3*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0008-0012
20
3*2.5+2.5
3*2.5+2.5
1.5-6
1.5-6
0.5-1.5
0.5-1.5
Table 3.8: Cable and fuse sizes for Vacon 10, 380 - 480 V, 3~
Frame
Type
Fuse
[A]
Mains
cable
Cu
[mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI3
0002-0004
6
3*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0005-0006
10
3*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0009
20
3*2.5+2.5
3*2.5+2.5
1.5-6
1.5-6
0.5-1.5
0.5-1.5
Table 3.9: Cable and fuse sizes for Vacon 10, 575 V
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...