58
•
vacon
parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
8.10 Protections (Control panel: Menu PAR -> P13)
NOTE!
These parameters are shown, when
P17.2 = 0.
8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14)
NOTE!
These parameters are shown, when
P17.2 = 0.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P13.1
Analog Input low
fault
0
2
1
700
0
= No action
1
= Alarm
2
= Fault: Coast
Under voltage
fault
1
2
2
727
1 =
No response (no fault
generated but drive still
stops modulation)
2 =
Fault:Coast
Earth fault
0
2
2
703 As parameter 13.1
Output Phase
Fault
0
2
2
702 As parameter 13.1
0
2
0
709 As parameter 13.1
0
2
0
713 As parameter 13.1
0
2
2
704 As parameter 13.1
-20
100
°C
40
705
Environment tempera-
tion
0,0
150,0
%
40,0
706 Cooling as % at 0 speed
1
200
min
45
707
Motor thermal time con-
stant
Table 8.10: Protections
Code
Parameter
Min
Max
Unit Default ID
Note
0
1
0
731
0
= Disabled
1
= Enable
Wait time
0,10
10,00
s
0,50
717 Waiting time after fault
0,00
60,00
s
30,00
718 Maximum time for trials
Restart Function
0
2
2
719
0
= Ramping
1
= Flying
2
= From Start Function
Table 8.11: Fault autoreset parameters
P13.2
P13.3
P13.4
i
i
i
i
i
i
P13.5
P13.6
P13.7
P13.8
P13.9
P13.10
P14.1
P14.2
i
i
P14.3
P14.5
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...