74
•
vacon
parameter descriptions
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
9
9.3 Frequency references (Control panel: Menu PAR -> P3)
3.3 R
EMOTE
CONTROL
PLACE
1
FREQUENCY
REFERENCE
SELECTION
It defines the selected frequency reference source when the drive is control-
led by the I / O terminal.
1 =
Preset speed 0
2 =
Keypad reference
3 =
Fieldbus Reference
4 =
AI1
5 =
AI2
6 =
PI
3.4 - 3.11 P
RESET
SPEEDS
0 - 7
Preset speeds 0 - 7 can be used to determine frequency references that are
applied when appropriate combinations of digital inputs are activated. Preset
speeds can be activated from digital inputs inputs when Par.3.3 (Remote con-
trol place frequency reference selection) =1.
Parameter values are automatically limited between the minimum and maxi-
mum frequencies. (par. 3.1, 3.2).
Table 9.1: Preset speeds 0 - 7
Speed
Preset
speed B2
Preset
speed B1
Preset
speed B0
Preset speed 0
Preset speed 1
x
Preset speed 2
x
Preset speed 3
x
x
Preset speed 4
x
Preset speed 5
x
x
Preset speed 6
x
x
Preset speed 7
x
x
x
Содержание 10
Страница 1: ......
Страница 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Страница 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Страница 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...