SECTION 1.6 Anchoring
1.6 ANCHORINg
1.6.1
Tie Patterns for unclad scaffolds
Every standard to be tied at top lift except where platform is greater than 1500mm from eaves.
•
End ties to be tied at maximum 4000mm crs
•
All ties to be within 300mm of standard - transom joint
• Good practice is to fix all ties to inner and outer standards. A minimum requirement is for all end ties to be fixed to
inner and outer standards and other ties fixed to inner standard only.
Denotes Tie Location
3500 max.
3500
3500
3500
3500
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
24000
4270 max.