Custom bindings
BAS-APG001-EN
129
UUKL binding list (actuator failure status)
Table 35 shows an example list of actuator failure status bindings.
Actuator failure status is sent directly from the mechanical system to the
FSCP.
UUKL binding list (FSCP control)
Table 36 shows an example list of smoke control panel control custom
bindings. Smoke control panel commands affect all MP581s panel control
units.
Table 35. Actuator failure status bindings
Function
Originator
Network variable
Destination
supplyFanFail
Mechanical system
nvoSwitch20
MP580-3/nviSwitch05
returnFanFail
Mechanical system
nvoSwitch21
MP580-4/nviSwitch04
oadamperFail
Mechanical system
nvoSwitch22
MP580-3/nviSwitch03
radamperFail
Mechanical system
nvoSwitch23
MP580-2/nviSwitch01
eadamperFail
Mechanical system
nvoSwitch24
MP580-4/nviSwitch02
stairFanFail
Mechanical system
nvoSwitch25
MP580-2/nviSwitch02
supplyDamperFloor01Fail
Mechanical system
nvoSwitch26
MP580-3/nviSwitch07
returnDamperFloor01Fail
Mechanical system
nvoSwitch27
MP580-3/nviSwitch08
supplyDamperFloor02Fail
Mechanical system
nvoSwitch28
MP580-3/nviSwitch10
returnDamperFloor02Fail
Mechanical system
nvoSwitch29
MP580-3/nviSwitch11
supplyDamperFloor03Fail
Mechanical system
nvoSwitch30
MP580-4/nviSwitch06
returnDamperFloor03Fail
Mechanical system
nvoSwitch31
MP580-4/nviSwitch07
supplyDamperFloor04Fail
Mechanical system
nvoSwitch32
MP580-4/nviSwitch09
returnDamperFloor04Fail
Mechanical system
nvoSwitch33
MP580-4/nviSwitch10
checkSupervisedCircuits
Mechanical system
nvoSwitch40
MP580-2/nviSwitch04
Table 36. Smoke control panel control custom bindings
Function
Originator
Network variable
Destination
lampTest
MP580-2
nvoSwitch01
MP580-3/nviSwitch40
nvoSwitch01
MP580-4/nviSwitch40
panel enable/disable
MP580-2
nvoSwitch03
MP580-3/nviSwitch36
nvoSwitch03
MP580-4/nviSwitch36
Содержание Engineered Smoke Control System
Страница 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 2: ......
Страница 3: ...BAS APG001 EN September 2006 Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 6: ......
Страница 12: ...Contents vi BAS APG001 EN ...
Страница 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Страница 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Страница 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Страница 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Страница 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Страница 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Страница 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Страница 104: ...Chapter 6 Installing the EX2 expansion module 92 BAS APG001 EN Figure 49 I O bus wiring example 2 ...
Страница 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Страница 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Страница 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Страница 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Страница 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Страница 154: ...Appendix A References 142 BAS APG001 EN ...
Страница 155: ......