Chapter 6 Installing the EX2 expansion module
94
BAS-APG001-EN
The EX2 module has four binary outputs, four analog outputs, and six
universal inputs.
Universal inputs
Each of the six universal inputs may be configured as binary.
Binary outputs
The four binary outputs are form A (SPST) relay outputs. These relays
are not dry contacts; they switch 24 Vac. A pilot relay is required for any
application using dry contacts. Relays connected to the binary outputs on
the EX2 cannot exceed 6 VA or 0.25 A current draw at 24 Vac.
Analog outputs (UUKL nondedicated only)
Each of the four analog outputs may be configured as either of the
following:
•
0–10 Vdc
•
0–20 mA
Analog output and universal input
setup
Configure each analog output and universal input using a LonTalk
ser-
vice tool, such as Trane’s Rover service tool. The service tool requires the
Tracer MP581 software plug-in to configure an EX2. EX2 modules receive
their configuration information from the Tracer MP581 controller they
communicate with. You can do online configuration with the Rover ser-
vice tool, or you can do offline configuration with Rover Configuration
Builder. In either case, the EX2 modules will not receive their configura-
tion until they are communicating with a configured Tracer MP581 con-
troller.
The inputs are factory configured to be not used. Analog outputs are con-
figured for voltage. Figure 51 on page 95 shows how to wire some common
sensor types and output devices.
Содержание Engineered Smoke Control System
Страница 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 2: ......
Страница 3: ...BAS APG001 EN September 2006 Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 6: ......
Страница 12: ...Contents vi BAS APG001 EN ...
Страница 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Страница 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Страница 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Страница 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Страница 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Страница 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Страница 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Страница 104: ...Chapter 6 Installing the EX2 expansion module 92 BAS APG001 EN Figure 49 I O bus wiring example 2 ...
Страница 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Страница 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Страница 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Страница 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Страница 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Страница 154: ...Appendix A References 142 BAS APG001 EN ...
Страница 155: ......