Chapter 7 Programming
118
BAS-APG001-EN
Nondedicated smoke purge
(UL-864: 3.21.h)
The term
nondedicated
refers to a system that provides the building’s
HVAC functioning under normal conditions and a smoke control objective
during a fire alarm condition.
The main concern when designing a nondedicated system is for
programming to ensure that, once a smoke alarm or FSCP override
occurs, any component of the smoke control system is controlled solely by
automatic smoke control or manual override commands. For details
regarding priority, see Table 28 on page 101.
Figure 70 shows an example of programming for a nondedicated system
to implement the priorities in Table 28. In this figure, the smoke control
dampers for Floor 1 are controlled. The actuator position, either Open or
Closed, will default to whatever the HVAC system commands. There are
two states that will turn control over to either automatic smoke control or
FSCP overrides:
•
If the broadcast general smoke alarm is TRUE, or
•
If the FSCP override switch is set to either Open or Closed.
Figure 70. Implementing priorities for a nondedicated system:
Controlling damper actuators
Содержание Engineered Smoke Control System
Страница 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 2: ......
Страница 3: ...BAS APG001 EN September 2006 Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 6: ......
Страница 12: ...Contents vi BAS APG001 EN ...
Страница 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Страница 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Страница 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Страница 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Страница 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Страница 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Страница 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Страница 104: ...Chapter 6 Installing the EX2 expansion module 92 BAS APG001 EN Figure 49 I O bus wiring example 2 ...
Страница 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Страница 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Страница 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Страница 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Страница 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Страница 154: ...Appendix A References 142 BAS APG001 EN ...
Страница 155: ......