Chapter 5 Installing the Tracer MP581 programmable controller
64
BAS-APG001-EN
Wiring inputs and outputs
The Tracer MP581 enclosure is designed to simplify the wiring and con-
figuration of inputs and outputs by providing a large space for routing
wires and by eliminating the need to manipulate jumpers. Table 16 lists
Tracer MP581 inputs and outputs.
Input/output wiring guidelines
Input/output wiring must meet the following guidelines:
•
Wiring must conform with the National Electrical Code and local elec-
trical codes.
•
Use only 18 AWG twisted-pair wire with stranded, tinned-copper con-
ductors.
•
Binary input/output wires must not exceed 1,000 ft (300 m).
•
Analog input wires must not exceed 300 ft (100 m) for thermistors
and 0–10 Vdc inputs and 1,000 ft (300 m) for 0–20 mA inputs.
•
Analog output wires must not exceed 1,000 ft (300 m) for 0–10 Vdc
outputs and 0–20 mA outputs.
•
Do not run input/output wires in the same wire bundle with high-
voltage power wires. Running input/output wires with 24 Vac power
wires is acceptable, but the input wire must be shielded.
•
Terminate input/output wires before installing the main circuit board
(see “Installing the circuit board” on page 76).
Table 16. Inputs and outputs
Type
Number
Description
Universal inputs
12
Dry-contact binary, thermistor,
0–20 mA, 0–10 Vdc, linear resistance.
The first four inputs can be used
directly with resistance temperature
detectors (RTDs).
Static pressure
input
1
Differential pressure sensor, 5 Vdc,
0–5 in. wc
Binary outputs
6
Powered relay contacts, 6 VA at 24 Vac
Analog outputs
6
0–10 Vdc or 0–20 mA
Содержание Engineered Smoke Control System
Страница 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 2: ......
Страница 3: ...BAS APG001 EN September 2006 Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 6: ......
Страница 12: ...Contents vi BAS APG001 EN ...
Страница 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Страница 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Страница 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Страница 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Страница 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Страница 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Страница 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Страница 104: ...Chapter 6 Installing the EX2 expansion module 92 BAS APG001 EN Figure 49 I O bus wiring example 2 ...
Страница 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Страница 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Страница 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Страница 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Страница 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Страница 154: ...Appendix A References 142 BAS APG001 EN ...
Страница 155: ......