Applications of smoke control methods
BAS-APG001-EN
9
Single and multiple injection pressurization techniques
The single injection and multiple injection techniques provide
pressurization air to a stairwell (Figure 6). Both techniques use one or
more pressurization fans located at ground level, roof level, or any
location in between.
The single injection technique supplies pressurization air to the stairwell
from one location.
IMPORTANT
The single injection technique can fail when stairwell access doors are
open near the air supply injection point. Pressurization air will escape
and the fan will fail to maintain a positive pressure difference across
access doors farther from the injection point.
The multiple injection technique supplies pressurization air to the
stairwell from more than one location. When access doors are open near
one injection point, pressurization air escapes. However, other injection
points maintain positive pressure differences across the remaining access
doors.
Figure 6: Sample single and multiple injection methods
Elevator shaft smoke control
Elevator shaft smoke control uses pressurization to prevent smoke
migration through elevator shafts to floors remote from the source of the
smoke. Elevator shaft smoke control is similar to stairwell smoke control.
The stairwell pressurization techniques described previously are
applicable to elevator shaft pressurization.
Designating an elevator as a fire exit route is an acceptable, though not
typical, practice. NFPA 101 (NFPA 2003,
Life Safety Code
) allows
elevators to be second fire exit routes from air traffic control towers. For
Содержание Engineered Smoke Control System
Страница 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 2: ......
Страница 3: ...BAS APG001 EN September 2006 Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 6: ......
Страница 12: ...Contents vi BAS APG001 EN ...
Страница 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Страница 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Страница 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Страница 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Страница 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Страница 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Страница 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Страница 104: ...Chapter 6 Installing the EX2 expansion module 92 BAS APG001 EN Figure 49 I O bus wiring example 2 ...
Страница 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Страница 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Страница 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Страница 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Страница 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Страница 154: ...Appendix A References 142 BAS APG001 EN ...
Страница 155: ......