Wiring inputs and outputs
BAS-APG001-EN
69
Wiring binary outputs
The Tracer MP581 controller has six binary outputs. These are powered
outputs, not dry-contact outputs.
IMPORTANT
Use pilot relays for dry-contact outputs when the load is greater than
6 VA or has a current draw of greater than 0.25 A. Use powered outputs
when the load is less than 6 VA or has a current draw of less than
0.25 A.
To wire a binary output:
1.
Connect the common wire to a common terminal as shown in
Figure 36.
2.
Connect the shield wire to a common terminal at the termination
board and tape it back at the output device.
3.
Connect the signal wire to an available binary output terminal
(BO1–BO6).
4.
Use the Rover service tool to configure the binary output.
Note:
When controlling coil-based loads, such as pilot relays, do not
forget to account for “inrush” current. Inrush current can be
three (or more) times greater than the operating current. You
can find information on inrush current for specific types of out-
puts in their product specifications.
Содержание Engineered Smoke Control System
Страница 1: ...BAS APG001 EN Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 2: ......
Страница 3: ...BAS APG001 EN September 2006 Applications Guide Engineered Smoke Control System for TRACER SUMMIT ...
Страница 6: ......
Страница 12: ...Contents vi BAS APG001 EN ...
Страница 30: ...Chapter 1 Smoke control overview 18 BAS APG001 EN ...
Страница 48: ...Chapter 3 Installation diagrams 36 BAS APG001 EN Figure 14 Tracer MP581 to FSCS wiring ...
Страница 50: ...Chapter 3 Installation diagrams 38 BAS APG001 EN Figure 15 Tracer MP581 to FACP wiring ...
Страница 57: ...Wiring high voltage ac power BAS APG001 EN 45 Figure 19 AC wiring ...
Страница 59: ...EMI RFI considerations BAS APG001 EN 47 Figure 20 Checking the earth ground ...
Страница 75: ...EMI RFI considerations BAS APG001 EN 63 Figure 31 Checking the earth ground ...
Страница 96: ...Chapter 5 Installing the Tracer MP581 programmable controller 84 BAS APG001 EN ...
Страница 104: ...Chapter 6 Installing the EX2 expansion module 92 BAS APG001 EN Figure 49 I O bus wiring example 2 ...
Страница 110: ...Chapter 6 Installing the EX2 expansion module 98 BAS APG001 EN ...
Страница 123: ...End process verification BAS APG001 EN 111 Figure 61 ast actuator fail checkb 3 13 06 ...
Страница 132: ...Chapter 7 Programming 120 BAS APG001 EN ...
Страница 151: ...Understanding bindings BAS APG001 EN 139 Figure 79 Mixed subnet node and group bindings ...
Страница 152: ...Chapter 8 Network variable bindings 140 BAS APG001 EN ...
Страница 154: ...Appendix A References 142 BAS APG001 EN ...
Страница 155: ......