67
Output current (effective value)
86A (failure) relay
Rated current
Overload pre-alarm output
OL operation time
OL operation time x c-11 / 100
150 %
■
c-12
Multifunction input
Display Contents
Setting range (Selecting item)
initialized
data
Unit
Write
during
operation
c-12
Multifunction input
terminal (1) [MI1]
function selection
0: External failure signal 1
(Protection relay 86A active)
1: External failure signal 2
(Protection relay 86A active)
2: External failure signal 3
(Protection relay 86A active)
3: External failure signal 4
(Protection relay 86A active)
4: External failure signal 1
(Protection relay 86A inactive)
5: External failure signal 2
(Protection relay 86A inactive)
6: External failure signal 3
(Protection relay 86A inactive)
7: External failure signal 4
(Protection relay 86A inactive)
8: Traceback external trigger
9: Emergency stop (B contact)
0
-
x
Multifunction input terminal (1) [MI1] function selection: c-12
In this parameter, set the function allocated to the multifunction input terminal (1) [MI1].