70
5.3.6.
Area E (control gain setting area)
In the area E, set the parameters related to the current control gain, DC voltage control gain, current command
upper/lower limit, etc.
■
E-00 through E-02
Current control gain settings
Display Contents
Setting range
(Selecting item)
Initialized
data
Unit
Write
during
operation
E-00
AC current control
proportional gain
0.0 to 9.9
5.0
-
○
E-01
AC current control
differential gain
0.0 to 9.9
0.0
-
○
E-02
AC current control
Integral gain
0.0 to 9.9
0.0
-
○
These are AC current control gains. Normally, do not change the initial values.
■
E-03 through E-07
Current/voltage control gain settings
Display Contents
Setting range
(Selecting item)
Initialized
data
Unit
Write
during
operation
E-03
DC voltage control
basic proportional gain
0.0 to 9.9
2.5
-
○
E-04
DC voltage control
maximum proportional gain
0.0 to 9.9
7.0
-
○
E-05
DC voltage control
variable ramp rate
0.0 to 9.9
3.0
-
○
E-06
DC voltage control
variable start voltage
0.0 to 40.0 (200 V class)
3.0
V
○
0.0 to 80.0 (400 V class)
6.0
E-07
DC voltage control
integral gain
0.0 to 9.9
1.0
-
○