50
6. Press the keys [
↑
] or [
↓
] to display "b-00."
7. Press the [
→
] key to blink numbers, and then press the keys [
↑
] or [
↓
] to change them to <b-03>.
・
For details of the operation command source selection: <b-03>,
refer to {5.3.3. Area b}.
8. Press the [SET] key.
・
The selection of <b-03> is confirmed, and a current setting
value ("0" to "2") is displayed. In default, "0" (terminal
block) is displayed.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless a setting value is
specified while it is displayed, it cannot be changed.
9. Press the keys [
↑
] or [
↓
] to confirm that the value is "0"
(terminal block).
10. Press the [SET] key.
・
The change is confirmed, and <b-03> is displayed again.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless the [SET] key is
pressed while a setting value is displayed, the change cannot
be confirmed.
11. Press the [MONI/FNC] key.
・
The [FNC] LED turns off, after a monitor item is displayed for about one second, its data appears.
12. Turn ON the external contact installed between the control
input terminal [START] and the terminal [PS] to start the
converter or turn it OFF to stop the converter.
Warning
Using the external contact
●
Note that if the power is turned on with a signal input to the control input terminal [START] on the terminal block,
the converter may suddenly start. After checking that no signal is input in the control input terminal [START], turn on
the power.
Otherwise, you may be injured.
External contact