135
2. Remove all wires.
・
Use the Phillips screwdriver (M3).
3. Short circuit all terminals on the main circuit terminal block.
・
For the terminal block and the position of terminals, refer to {3.3.1. How to Connect Converter Terminals}.
4. Measure insulation resistance between the terminals on the main circuit terminal block and the protective
earth terminal.
・
Check that insulation resistance is more than or equal to 10 M
Ω
.
・
If it is less than 10 M
Ω
, contact us.
5. Remove all short-circuit wires.
6. Return the wires to the original state.
7. Close the front cover.