61
■
b-03 through b-06
Command source selection
Display Contents
Setting range (Selecting item)
Initialized
data
Unit
Write
during
operation
b-03
Operation command
source selection
0: Terminal block
1: Console
2: Digital communication option
0
-
x
b-04
DC voltage command
source selection
0: Console
1: Digital communication option
2: Internal PLC
0
-
x
b-05
Active current
command
source selection
0: Standard (DC voltage command)
1: Digital communication option
2: Internal PLC
3: Analog input (2) terminal [AIN2]
4: Analog input (3) terminal [AIN3]
0
-
x
b-06
Reactive current
command
source selection
0: Standard (power-factor setting)
1: Digital communication option
2: Internal PLC
3: Analog input (2) terminal [AIN2]
4: Analog input (3) terminal [AIN3]
0
-
x
Select the command source for operation, DC voltage, active current and reactive current.
Operation command source selection: b-03
In this parameter, select the operation command source.
With "0: Terminal block" selected, an operation command is given by an input to the terminal [START].
With "1: Console" selected, an operation command is given by the [START] key on the console.
With "2: Digital communication option" selected, an operation command is given by an input of the digital
communication option.
In using the PLC-L or PLC-H function, an operation command is given by an output of the PLC function regardless
of the operation command source selection: b-03.
DC voltage command source selection: b-04
In this parameter, set the DC voltage command source.
With "Console" selected, the setting of DC voltage command fixed mode d-00 is followed.
With "Digital communication option" selected, digital communication option needs to be selected for the digital
communication option selection: J-00.
With "Internal PLC" selected, the PLC-L function: b-01 or PLC-H function: b-02 needs to be set to ON.
Active current command source selection: b-05
In this parameter, set the active current command source.
With "Standard" selected, an active current command is determined by the DC voltage control.
With "Digital communication option" selected, digital communication option needs to be selected for the digital
communication option selection: J-00.
With "Internal PLC" selected, the PLC-L function: b-01 or PLC-H function: b-02 needs to be set to ON.
With "Analog input (2) terminal" or "Analog input (3) terminal" selected, digital communication option needs
to be selected for the digital communication option selection: J-00.