62
Reactive current command source selection: b-06
In this parameter, set the reactive current command source.
With "Standard" selected, a reactive current command is determined by the power-factor control.
With "Digital communication option" selected, digital communication option needs to be selected for the digital
communication option selection: J-00.
With "Internal PLC" selected, the PLC-L function: b-01 or PLC-H function: b-02 needs to be set to ON.
With "Analog input (2) terminal" or "Analog input (3) terminal" selected, digital communication option needs
to be selected for the digital communication option selection: J-00.
■
b-07 and b-08
Selection of restart after instantaneous power interruption during operation
Display Contents
Setting range (Selecting item)
Initialized
data
Unit
Write
during
operation
b-07
Selection of restart
after instantaneous
power interruption
0: Enable
1: Disable
0
-
x
b-08
For special
adjustment
*
-
-
-
-
*: Do not set this item.
Selection of restart after instantaneous power interruption: b-07
Select the action taken when a drop in DC voltage or abnormality in the AC power supply occurs.
OFF: Performs the protection operation against power supply abnormality. The 86A contact is turned ON. Resetting
is required to recover after the power is restored.
ON: Performs the protection operation against power supply abnormality, but the 86A contact is not turned ON.
An automatic reset is performed after the power is restored.
Warning
About restart after instantaneous power
interruption
●
When the selection of restart after instantaneous power interruption: b-07 is set to "0: Used," the operation is restarted
automatically after the power is restored from instantaneous power interruption. Do not come close to the converter output
part while instantaneous power interruption is detected.
Otherwise, you may be injured.