99
2. Press the keys [
↑
] or [
↓
] to display "L-00."
3. Press the [
→
] key to blink numbers, and then press the keys [
↑
] or [
↓
] to change them to "L-07."
・
For details of the analog input (2) characteristics selection:
L-07, refer to {5.3.10. Area L}.
4. Press the [SET] key.
・
The selection of "L-07" is confirmed, and the current setting
value (Initialized data is "0") is displayed.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless a setting value is
specified while it is displayed, it cannot be changed.
5. Press the keys [
↑
] or [
↓
] to change the number to "0" (0 to
10 V).
6. Press the [SET] key.
・
The change is confirmed, and "L-07" is displayed again.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless the [SET] key is
pressed while a setting value is displayed, the change cannot
be confirmed.
7. Turn off the converter.
8. Open the front cover.
・
For how to open the front cover, refer to {3.2. How to Open and Close Front Cover}.
・
Use the Phillips screwdriver (M4).
9. Short circuit the terminals [AIN2], [G], and [G-IN] on the terminal block of <IO66-Z>.
・
For the terminal block and the position of terminals, refer to
{3.3.1. How to Connect Converter Terminals}.
・
Use the Phillips screwdriver (M3).