80
■
L-03 through L-06 and L-09 through L-12
Analog input/output gain and offset adjustment
Display Contents
Setting range (Selecting item)
Initialized
data
Unit
Write
during
operation
L-03
Analog_output(2)
gain
50.0 to 150.0
100.0
%
○
L-04
Analog_output(2)
offset
-50.0 to 50.0
0.0
%
○
L-05
Analog_output(3)
gain
50.0 to 150.0
100.0
%
○
L-06
Analog_output(3)
offset
-50.0 to 50.0
0.0
%
○
L-09
Analog_input(2)
gain
50.00 to 150.00
100.00
%
○
L-10
Analog_input(2)
offset
-50.00 to 50.00
0.00
%
○
L-11
Analog_input(3)
gain
50.00 to 150.00
100.00
%
○
L-12
Analog_input(3)
offset
-50.00 to 50.00
0.00
%
○
L-03 through L-06, and L-09 through L-12 are setting areas for adjusting analog input/output gain and offset.
These values are automatically set when analog output adjustment for the area S or analog input adjustment is
performed. Therefore, normally you do not have to set them manually.
■
L-07 and L-08
Analog input characteristics selection
Display Contents
Setting range (Selecting item)
Initialized
data
Unit
Write
during
operation
L-07
Analog input (2) (3)
characteristics selection
0: 0 to
±
10 V
0
-
x
L-08
For special adjustment
*
-
-
-
-
*: Do not set this item.
Analog input characteristics selection: L-07
With these parameters, select the characteristics of the signal input to the analog input terminal. For details,
refer to the manual of digital communication option.