102
30. Press the [SET] key.
・
The password input is confirmed, and the screen returns to
"S-05" display.
・
When a different number from "1040" is input, "P-Err" indicating
an error is displayed. In this case, press the keys [
↑
] or [
↓
]
to return to "S-05."
Follow the procedures again from the step 28.
Display indicating a password error
31. Press the [SET] key.
・
"0" is displayed on the extreme right, and the underscore blinks
on the extreme left.
32. Apply 10 V with the voltage generator and press the [
→
] key to blink required digits, and then press the
keys [
↑
] or [
↓
] to specify a value 1000 times a value measured by the voltage meter or the tester.
・
Inputting a value 1000 times a voltage value of the analog input
(2) enables gain adjustment of the analog input (2).
Specify "9983" if the measured value is 9.983V
33. Press the [SET] key.
・
When "S-05" is displayed again, the settings of the analog input
(2) gain: L-9 and analog input (2) offset: L-10 are
automatically changed.
34. Press the [MONI/FNC] key.
・
The [FNC] LED turns off, after a monitor item is displayed for about one second, its data appears.
35. Turn off the converter, and open the front cover.
36. Remove the wire attached to the terminals [AIN2], [G] and [G-IN] on <IO66-Z>.
37. Remove the installed DC voltage meter or tester.
38. Close the front cover.