65
■
c-07 and c-08
Multifunction output
Display Contents
Setting range (Selecting item)
initialized
data
Unit
Write
during
operation
c-07
Multifunction output
terminal (3)
[MO3] function
selection
0: Pulse output upon arrival of integrated
power setting
1: During power failure
2: Overload pre-alarm
3: (For special adjustment)
*1
4: Sum check error
5: In operation
6: Timer 1 elapsed
7: Timer 2 elapsed
8: Cooling fan failure
0
-
x
c-08
Multifunction output
terminal (4)
[MO4] function
selection
1
-
x
*1: Do not set this item.
Install and set the digital communication option to use the function of multifunction output terminal.
For how to set the digital communication option, refer to {5.3.11. Area J}.
The above "1" (During power failure) is output when the DC voltage is at a power failure level of 180 V (360
V for 400 V class) or less with normal control power supply, or the AC power supply is not established.
Multifunction output terminal (3) [MO3]: c-07 and (4) [MO4] function selection: c-08
In these parameters, set the function allocated to the multifunction output terminal (3) [MO3] and (4) [MO4].