47
4.3.
Operations on Console
This section provides operating procedures for the converter from the console.
When the converter can be operated from the console, the [DIR] LED turns on.
・
When the [DIR] LED turns off, refer to {5.3.3. Area b}.
■
Operation flow
Preparation/wiring
Check capacity/voltage/
converter mode you use
Power on
Check VF66R
capacity/voltage/converter mode
Set DC voltage, power factor,
power supply frequency,
power supply voltage reference value,
etc.
Run/stop
Perform wiring between the converter and DC power supply (+, -),
between the converter and power supply (L1/R, L2/S, L3/T), ground
terminal
, AC power supply voltage detection transformer, switch,
etc.
<Capacity>
<Voltage>
<Converter mode>
Press the [MONI/FNC] key on the console panel
to turn on FNC [LED] and set "0.VrEF"
(DC voltage command), "1.PHi" (power-factor
angle), "2.FrEq" (power supply frequency),
etc.
Press the [MONI/FNC] key on the console panel
to turn off FNC [LED] and press the [START]
key to start operation with the specified
DC voltage command (0.VrEF), power-factor
angle (1.PHi), etc. Press the [STOP/RESET]
key to stop the operation.
Change setting