- 20 -
tousek
/ E_TPS-20_03 / 30. 08. 2016
Important: Photocells notes
•
The control unit has a power supply connection for a 24V a.c. photocell (LS):
supply LS-transmitter: terminals 41/42 / supply LS-receiver: terminals 43/44
Note: in „gate closed“ position the terminals 41/42 are being switched into energy saving mode (no current)
(only, if no TX 310 system is used) !
• The contact has to be closed when using powered and positioned photocells (opening contact).
Connection of the photocell contact: terminals 45/46, photocell back area contact: terminals 45/48
• When using two pairs of photocells please do not
install both photocell transmitters/receivers on the
same side (to eleminate interference between both) !
Exception: photocells with SYNC function allow the
installation of both photocell transmitters/receivers on
the same side without causing interference to each
other.
• Photocell self-test function:
The control board is equipped with a self-test function for the connected photocell. With an
opening impulse (switch or button) the transmitter of the photocell is switched off for a short time in gate position „closed“
. Thus the photocell receiver interrupts the contact 45/46 and 45/48 (PHC- back area) - so the control board verifies
the function of the photocell receiver. If this short interruption at the photocell input is not carried out, the control board
reports an error.
The deactivation of the self-test function is only allowed if the safety installations correspond
to the category 3 !
• The exact function of the photocells depend on the programming of the control unit.
Photocell function please see
menu point SAFETY / photocell function or photocell with pause time
• you will find detailed information in the corresponding photocell manual.
G
Photocell
(contact: terminals 45/46)
Safety
active:
to be selected, if photocell should be triggered.
not active:
to be selected, if photocell should not be triggered..
PHC- back area
(contact: terminals 45/48)
Safety
not active:
No monitoring by PHC-back area.
active:
To be selected, if the back area of the gate has to be protected by a photocell during the opening movement.
An interruption of the photocell during the opening movement causes the motor to get stopped and remain stopped
as long as the photocell is interrupted. After releasing the photocell, the gate opens.
PHC-function (only photocell at terminals 45/46 is concerned)
Safety
when closing reverse:
an interruption of the photocell during closing makes the gate reverse (open). In automatic
mode the gate closes as soon as the pause time has run out. In impulse operation another closing command has to
be given.
stop, after release open
:
an interruption of the photocell beam during opening or closing makes the motor stop as long
as the photocell stays interrupted. After release of the photocell, the gate opens. In automatic mode the gate closes as
soon as the pause time has run out, in impulse operation another closing command has to be given.
during closing stop then close
:
an interruption of the photocell during closing makes the motor stop as long as the
photocell stays interrupted. After release of the photocell, the gate closes.
photocell
PHC- back area
CLOSE OPEN
Safety
Connections and adjustments
Standard:
transmitter 1
receiver 1
receiver 2
transmitter 2
With SYNC-function:
transmitter 1
receiver 1
transmitter 2
receiver 2