5.5.1. Temperature monitoring menu
Line 1
T E M P . C O N T R O L
Line 2
O f f
Line 3
O f f
Line 4
T e m p . - O k : - 8 8
K
Line 5
5 - 9 9 K + 8 8
K
Line 6
D e l a y : 8 8 . 8 s
Line 7
0 - 9 9 . 9 s
Line 8
Press the button
to return to the Monitoring menu (
5.5.).
Line 1:
Menu name
Line 2…3:
Options for switching the temperature monitoring
on and off.
Line 4…5:
Setting of the upper and lower limit of the tem-
perature Ok-range around the desired value for the temper-
ature monitoring. The adjustable range is shown in line 5.
Line 6…7:
Setting of the delay time for the temperature
monitoring. The temperature monitoring will only be activat-
ed after this delay time has elapsed. The delay time is start-
ed as soon as the actual value is within the temperature Ok-
range. The adjustable range is shown in line 7.
5.5.2. Heating monitoring menu
Line 1
P R E H E A T . C O N T R O L
Line 2
O f f
Line 3
O f f
Line 4
T e m p . - O k : - 8 8
K
Line 5
5 - 9 9 K + 8 8
K
Line 6
P r e h . t i m e : 8 8 . 8 s
Line 7
0 - 9 9 . 9 s
Line 8
Press the button
to return to the Monitoring menu (
5.5.).
Line 1:
Menu name
Line 2…3:
Options for switching the heating monitoring on
and off.
Line 4…5:
Setting of the upper and lower limit of the tem-
perature Ok-range around the desired value for the heating
monitoring. The adjustable range is shown in line 5.
Line 6…7:
Setting of the admissible heating time; the actual
value should be within this temperature Ok-range. The ad-
justable range is shown in line 7.
5.6. In-/Output settings menu
Zeile 1
E I N - / A U S G Ä N G E
Zeile 2
R e l a y s e t t i n g
Zeile 3
I n p u t s e t t i n g
Zeile 4
Zeile 5
Zeile 6
Zeile 7
Zeile 8
Press the button to return to the Selection menu (
5.3.).
Line 1:
Menu name
Line 2:
Menu item “Relay setting” (
5.6.1.)
Line 3:
Menu item “Input setting” (
5.6.1.)
5.6.1. Relais setting menu
Line 1
R E L A Y S E T T I N G
Line 2
M e s s a g e r e l a y 1
Line 3
C o n t r o l r e l a y 1
Line 4
C o n t r o l r e l a y 2
Line 5
A l a r m r e l a y
Line 6
S t a t u s r e l a y o u t p u t
Line 7
Line 8
Press the button to return to the In-/Output settings menu
(
5.6.).
Line 1:
Menu name
Line 2:
Menu item “Message relay 1 setting” (
5.6.1.1.)
Line 3:
Menu item “Control relay 1 setting” (
5.6.1.2.)
Line 4:
Menu item “Control relay 2 setting” (
5.6.1.2.)
Line 5:
Menu item “Alarm relay setting” (
5.6.1.3.)
Line 6:
Menu item “Status displ. relay outputs” (
5.6.1.4.)
5.6.1.1. Message Relay 1 settings menu
Line 1
ME S S A G E R E L A Y 1
Line 2
O o n t a c t :
N O C
Line 3
N C
Line 4
O f f
Line 5
T e m p . f u n c t i o n
Line 6
S e q u n c e f u n c t i o n
Line 7
T i m e P u l s e f u n c t i o n
Line 8
Press the button
to return to the Relay settings menu (
5.6.1.).
Line 1:
Menu name
Line 2…3:
Options for the switching mode of the relay; the
relay can be set as NO or NC when the corresponding func-
tion is activated.
Line 4:
Option of the message relay is deactivated
Line 5:
Selection and menu items (
5.6.1.1.1.) of the
temperature functions for the message relay.
Line 6:
Selection and menu items (
5.6.1.1.2.) of the se-
quence functions for the message relay.
Line 7:
Selection and menu items (
5.6.1.1.3.) of the time
pulse function for the message relay.