The information of the attributes present is shown in the following:
Specific Trap #1:
Attribute #1 – MIB value upsBatteryStatus. Integer value 1 to 4 that indicates battery
health.
Attribute #2 – MIB value upsSecondsOnBattery. Integer value that represents the
amount of time, in consecutive seconds, that the UPS has been in battery backup
operation mode.
Attribute #3 – MIB value upsEstimatedMinutesRemaining that represents the amount
of time, in minutes, that the UPS can currently provide battery backup, should backup
operation be necessary.
Specific Trap #2:
Attribute #1 – MIB value upsTestID. Integer value that represents the test. This
number resets to value 0 each time RemotEye II is reset.
Attribute #2 – MIB value upsTestSpinLock. Integer value that acts as a key granting
or refusing permission to initiate a test.
Attribute #3 – MIB value upsTestResultsSummary. Integer value that represents the
results of a test.
Specific Trap #3:
Attribute #1 – MIB value upsAlarmID. This is an integer representing the sequence
in which the trap was added to the alarms browser. This sequence will repeat when
the agent is reset.
Attribute #2 – MIB value upsAlarmDesc. This is a MIB Description (whether
numerical or textual) of the fault that has added.
Specific Trap #4:
Attribute #1 – MIB value upsAlarmID. This is an integer representing the sequence
in which the trap was cleared from the alarms browser. This sequence will repeat
when the agent is reset.
Attribute #2 – MIB value upsAlarmDesc. This is a MIB Description (whether
numerical or textual) of the fault that has cleared.