91
UPS Alarm List
ID Object
Alarm Occur Message
Alarm Removal Message
1 …/upsAlarmBat
teryBad
Battery test has detected
battery failure. Contact
Toshiba authorized service
center for replacement.
Battery failure condition, detected
by previous battery test, has been
removed.
2 …/upsAlarmOn
Battery
The UPS is on batteries; it is
supplying output power from
its batteries.
The UPS is no longer on batteries;
output power is not being supplied
from its batteries.
3 …/upsAlarmLo
wBattery
Low battery. Continued
operation on batteries will
deplete them entirely & result
in UPS Output shutdown.
The UPS is no longer reporting a
state of Low Batteries.
4 …/upsAlarmDe
pletedBattery
UPS has depleted batteries &
unable to support critical
loads. Turn off excess
equipment to reduce load.
The batteries are no longer
depleted; they have been charged to
a supportive level.
5 …/upsAlarmTe
mpBad
The UPS is overheating.
Check for UPS fan failure or
high ambient temperature ( >
40°C / 104°F)
The UPS is no longer overheating.
6 …/upsAlarmInp
utBad
The input voltage is out of
tolerance. UPS may switch to
Battery Mode to support the
load.
The input voltage is back within
tolerance.
7 …/upsAlarmOu
tputBad
The output voltage is out of
tolerance. Check the output
voltage.
N/A
8 …/upsAlarmOu
tputOverload
UPS is overloaded. UPS will
switch to bypass or shutdown.
Turn off excess equipment to
reduce load.
The UPS is no longer being
overloaded.
9 …/upsAlarmOn
Bypass
The UPS is in Stop (Bypass)
mode.
The UPS is no longer in Stop
(Bypass) mode.
10 …/upsAlarmBy
passBad
A bypass condition is out of
tolerance. Check the input
and output voltage.
N/A