Daily Status – Daily History log and Events log will be sent to the email recipients at
the designated time.
Events with Status – Current events, History log and Events log will be sent to email
recipients when events occurred
EMD Configuration
Comprehensive View
This page gives a snapshot of all EMD parameters; the parameters will be updated
automatically every 5 seconds.
The text color of the parameter indicates its status based on the administrator-
configurable threshold.
The list below indicates the parameter status.
GREEN : 'normal' status.
YELLOW : 'warning' status,
RED : 'critical' status.
GREY : 'unknown' value.
The EMD provides the measurements for room temperature, room humidity,
and two alarms.
The warning/critical thresholds can be setup via the "EMD Setup" page.
EMD Setup
This page allows administrator to configure all necessary parameters of an EMD.
Set Point
The threshold of a sensor (temperature or humidity) will trigger an alarm, whenever
the measurement is over (high) or under (low) the set point. The alarm can be
configured to activate at warning or critical levels. If the checkbox is not filled, the
threshold is disabled and the alarm will not be triggered. The valid range for the
Temperature threshold setting is 5 to 65, and 5 to 95 for Humidity.
Hysteresis
A sensors value could be floating around its threshold triggering multiple alarms.
Setting the hysteresis will help to prevent the alarm bouncing between active and
inactive. For example, if the low warning threshold set point is 20 and hysteresis is 3,
then the alarm will activate when the value reaches 20 but it will not become inactive
again until the sensor value reaches 23.