Number of Batteries in Series
This field allows the administrator to configure the total number of batteries in series
of the UPS system.
Number of Batteries in Parallel
This field allows the administrator to configure the total number of batteries in parallel
of the UPS system.
Battery Rated Backup Time
This field allows the administrator to configure the estimated battery backup time (in
minutes) during power failure at 100% load.
UPS Control
This page lists the automatic switching and shutdown parameters.
UPS Output Shutdown Delay
This field allows the user to configure or view the delay (in seconds) of the UPS
switching from the Run (Inverter) mode to the Output Shutdown mode after receiving
the Output Shutdown command. The UPS output shutdown delay time count down
will be synchronized with the output shutdown delay time setting in the RemotEye II
Shutdown Service program for all connected clients. To avoid improper output
shutdown of the clients, the UPS output shutdown delay time setting in the RemotEye
II should always be greater than the RemotEye II Shutdown Service program's
shutdown delay setting. Please refer to RemotEye II manual for instruction on how to
setup RemotEye II Shutdown Service.
Set UPS to Output Shutdown Mode after Delay (option)
This option switches the UPS from the Run (Inverter) mode to the Output Shutdown
mode.
UPS Run (Inverter) Mode Delay
This field allows the administrator to configure or view the duration (in minutes) of
the UPS switching from the Output Shutdown mode to the Run (Inverter) mode after
receiving the Run (Inverter) command.
Set UPS to Run (Inverter) Mode after Delay (option)
This option switches the UPS from Output Shutdown mode to the Run (Inverter)
mode.
Set UPS to Run (Inverter) Mode AND Cancel Any Impending Shutdown
(option)
This option cancels any impending shutdown to the UPS and set the UPS to Run
(Inverter) mode.