Managing the UPS Recurring & Non-recurring Schedule
RemotEye II supports two output shutdown schedule – (1) Recurring Schedule; (2)
Non-recurring Schedule.
Note: Before managing the UPS Shutdown Schedule, please make sure that the Date
and Time configured in RemotEye II is correct.
Scenario
Shutdown Event:
Recurring Schedule
Status:
UPS
Output
shutdown
Delay
(Min):
10(default)
Warning Interval (sec):
60(default)
UPS Shutdown Delay (Sec):
180(default)
Shutdown & Restart day & time: Monday 22:20:00 ----- 99:99:99
Shutdown & Restart day & time: Tuesday
99:99:99 ----- 09:00:00
Note: 99:99:99 indicates the RemotEye II will ignore the Restart Time on Monday,
and the Shutdown time on Tuesday.
Monday
Tuesday
22 : 20 : 00 22 : 30 : 00 22 : 33 : 00 09:00:00
OUTPUT
SHUTDOWN
INVERTER