86
Granting Write Access
The RemotEye II controls permissions for workstations. Any workstation attempting
to alter UPS parameters through RemotEye II must have permission.
By default, the RemotEye II will allow any workstation the ability to write new
configuration information to RemotEye II and its attached Toshiba UPS. This is
accomplished through SNMP sets using the default read/write community string.
To restrict access to only NMS machines, the SNMP Communities and Control
Group of RemotEye II must be programmed accordingly. See the section entitled
SNMP Communities on page 38 for details on adding workstations to the SNMP
Communities.
If the IP address of the NMS is not added to the SNMP Communities with Read/Write
permissions, the NMS software can only read the status of the UPS, and changes to
UPS parameters will be prohibited.