Setup for outdoor unit with trouble
3
Service valves of the liquid and the
balance pipe are kept opened.
(However close the liquid valve when a
leakage occurred on the outdoor PMV.)
4
Remove communication connector
[CN03] on the interface P.C. board
only when a trouble occurred on
the refrigerant circuit parts system.
2
Close service
valve of gas
pipe fully.
11-3. Outdoor Unit Backup Setup
<Outline>
Against a case that a trouble occurs on the outdoor unit, backup operation can be set up to either header unit or follower
unit. For the multiple outdoor unit system (Failure of compressor coil), perform an outdoor unit backup operation if the
following error modes occurred.
• Trouble on compressor
• Trouble on pressure sensor (Pd, Ps) /temperature sensor (TD1, TD2, TS1, TE1, TK1, TK2, TK3, TK4, TL)
Note: Backup of the outdoor unit should be restricted to one unit in one system.
11-3-1. In case of Trouble on Follower Outdoor Unit
(Backup setup for follower outdoor unit)
<Work procedure>
1. Turn off the main power supplies of all the units connected to the system.
[Setup for outdoor unit with trouble]
2. Close fully the gas side service valve of the unit with trouble.
3. Leave service valve of the balance pipe of the liquid pipe opened. (To prevent refrigerant stagnation in the unit)
However close fully service valve of the liquid pipe when there is PMC leakage in outdoor unit (PMV does not close.).
4. <In case of trouble on the compressor or electric parts system (Compressor, electric system parts, I/F P.C. board, IPDU
P.C. board)>
After then, keep OFF for the main power supply of the unit with trouble.
<In case of trouble on the refrigerant circuit parts system (Pressure sensor, temperature sensor, refrigerat circuit parts,
fan system parts)>
Remove the communication (BUS2) connector [CN03] between outdoor units on the interface P.C. board.
[Setup for header unit]
5. Turn on Bit 2 of the Dip SW09 on the interface
P.C. board of the header unit.
(Setup not to detect the indoor capacity over)
6. Turn on the power supplies of all the units other
than the unit with trouble.
As for power supply of the unit with trouble,
follow the procedure below.
<In case of trouble on the compressor or
electric parts system (Compressor,
electric system parts, I/F P.C. board,
IPDU P.C. board)> Keep OFF for the main power supply of the unit.
<In case of trouble on the refrigerant circuit parts system (Pressure sensor, temperature sensor, refrigerant
circuit parts, fan system parts> Turn on the power supply to protect the compressor. (Case heater ON)
(Although [E19] (Outdoor header unit quantity error) is displayed on 7-segment display after turning on the
power supply of the unit, it is not a problem because it is only interruption of communication with the
header unit.)
Interface P.C. board of the header unit
5
Turn on Bit 2 of Dip
SW09.