97
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor cabling work and unpracticed outdoor
cabling work (Manual setup from remote controller)
Arrange one indoor unit and one remote controller set to 1 by 1.
Turn on the power.
1
Push simultaneously
SET
+
CL
+
buttons for 4 seconds or more.
LCD changes to flashing.
(Line address)
2
Using the setup temp.
/
buttons, set
12
to the item code.
3
Using the timer time
/
buttons, set
up the line address.
(Match it with the line address on the interface
P.C. board of the header unit in the identical
refrigerant line.)
4
Push
SET
button.
(OK when display goes on.)
(Indoor address)
5
Using the setup temp.
/
buttons, set
13
to the item code.
6
Using the timer time
/
buttons, set
up the indoor address.
7
Push
SET
button.
(OK when display goes on.)
(Group address)
8
Using the setup temp.
/
buttons, set
14
to the item code.
9
Using the timer time
/
buttons, set
Individual =
0000
, Header unit =
0001
,
Follower unit =
0002
.
10
Push
SET
button.
(OK when display goes on.)
11
Push
button.
Setup operation finished.
(Status returns to normal stop status.)
UNIT
SET
CL
UNIT No.
CODE No.
SET DATA
R.C.
No.
Operation procedure
1 2 3 4 5 6
7 8 9 10 11
End
2, 5, 8
3, 6, 9
1
4, 7, 10
11
Data
Item code
Outdoor
Header
#1
Indoor
Indoor
Indoor
Line address
1
Indoor address
1
Group address
1
Outdoor
#2
Indoor
Indoor
Terminal
1
2
2
1
3
2
2
1
2
2
2
2
Remote
controller
(Wiring example in 2 lines)
In the above example, under condition of
no inter-unit wire of the remote controller,
set the address after individual connect-
ing of the wired remote controller.
Group address
Individual
: 0000
Center unit
: 0001
Terminal unit : 0002
}
In case of group control
Содержание MMC-AP0151H
Страница 270: ......