114
8-7-2. Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit
The following functions of the indoor unit can start or stop by the switches on the interface P.C. board of the header unit.
NOTE 1) This start/stop function only sends the signals from the outdoor unit to the indoor unit, such as start, stop,
operation mode, etc. It does not resend the signals even if the indoor unit does not follow the sent signals.
NOTE 2) The above controls are not used during abnormal stop.
No.
1
2
3
4
Function
Cooling test
operation
Heating test
operation
Batch start
Batch stop
Individual
start
Individual stop
Individual test
operation
Outline
Changes the mode of all the connected indoor
units collectively to cooling test operation.
Note) Control operation same as usual test
operation from remote control is
performed.
Changes the mode of all the connected indoor
units collectively to heating test operation.
Note) Control operation same as usual test
operation from remote control is
performed.
Starts all the connected indoor units collec-
tively.
Note) The contents follow to the setup of
remote controller.
Stops all the connected indoor units collec-
tively.
Starts the specified indoor unit.
Notes)
• The contents follow to the setup of remote
controller.
• The other indoor units keep the status as
they are.
Stops the specified indoor unit.
Note) The other indoor units keep the status
as they are.
Operates the specified indoor unit.
Note) The other indoor units keep the status
as they are.
Setup/Release
[Setup]
Push SW04 for 2 seconds or more
with SW01”2”, SW02”5”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 2 seconds or more
with SW01”2”, SW02”6”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 2 seconds or more
with SW01”2”, SW02”7”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW05 for 2 seconds or more
with SW01”2”, SW02”7”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 2 seconds or more set
SW01 “16” and set SW02 and SW03
to address No. (1 to 64) to be started.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW05 for 2 seconds or more set
SW01 “16” and set SW02 and SW03
to address No. (1 to 64) to be stopped.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 10 seconds or more
set SW01 “16” and set SW02 and
SW03 to address No. (1 to 64) to be
operated.
[Release]
Return SW01, SW02, SW03 to “1”.
7-segment display
Section A
Section B
[C ]
[ –C]
Section A
Section B
[H ]
[ –H]
Section A
Section B
[CH]
[ 11]
[ 11] is displayed on
Section B for 5 seconds.
Section A
Section B
[CH]
[ 00]
[ 00] is displayed on
Section B for 5 seconds.
Section A
Section B
[ ]
[ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 11] for 5 seconds
from operation-ON.
Section A
Section B
[ ]
[ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 00] for 5 seconds
from operation-OFF.
Section A
Section B
[ ]
[ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ FF] for 5 seconds
from test operation-ON.
Interface P.C. board
7-segment display [A]
7-segment display [B]
SW04
SW05
SW01 SW02 SW03
<Rotary switch>