Operation start
Push the push-switch SW04 on the interface P.C. board of
the header unit for 2 seconds or more. The operation starts.
Check that cooling is [ CC] and heating is [ HH] on
7-segment display [B].
(7-segment display)
[A]
[ ]
C or H
[B]
[ # # P ]
No. of
misconnected
indoor units
(7-segment display)
[A]
[ ]
C or H
[B]
[ # #]
Address display
of misconnected
indoor unit
(7-segment display)
[A]
[ U1 ]
[B]
[ ]
Confirmation of check results (1)
Check that No. of misconnected indoor units is displayed
on 7-segment display [B] after 15 minutes.
(If there is no misconnection, [00P] is displayed.)
Confirmation of check results (2)
Push the push-switch SW05 on the interface P.C. board of
the header unit for 2 seconds or more.
The indoor address in which error is being detected is
displayed on 7-segment display [B]. If there are multiple
indoor address in which error is being detected, they are
successively exchanged and displayed.
(When SW05 is turned on again, the display returns to
display of No. of units.)
After check, set each rotary switch SW01, SW02, SW03 to
1/1/1.
(7-segment display)
[A]
Cooling [ C ]
Heating [ H ]
[B]
[ CC ]
[ HH ]
A
Operation
This check operation
requires 15 minutes even
if there is no misconnection
or there is any misconnection.
Interface P.C. board
7-segment display [A]
7-segment display [B]
SW04
SW05
SW01 SW02 SW03
<Rotary switch>