125
NOTE) Emergent operation should be restricted to one day or so on. If operating TO sensor fixed with this
function, the system control operation of the air conditioner may not become one based upon the
specification of the product. Therefore an emergent operation should be restricted to a day or so on.
2. Keep pushing the push-switch SW04 on the interface P.C. board for 1 second or more.
The mode changes to the TO sensor value fix manual mode.
3. As shown in the following table, TO sensor value can be fixed by setting the rotary switch SW02 on the
interface P.C. board.
[Clear]
Return numbers of SW01, SW02, and SW03 on the interface P.C. board in the outdoor unit to [1/1/1] each.
<Service support function list>
SW01
2
2
2
2
16
SW01
1
SW02
1
2
3
4
5
6
7
11
16
1 to 16
1 to 16
SW-2
1
SW03
1
3
4 to 5
15
1
2
3
4
SW03
1
7-segment display [A]
[ J
C ]
[ J
H ]
[ P
]
[ A
1 ]
[ C
]
[ H
]
[ C
H ]
[
r
d ]
[ E
r
]
[ H
r
]
[ F
d ]
[
t
o ]
[ 0 1] to [ 1 6 ]
[ 1 7] to [ 3 2 ]
[ 3 3] to [ 4 8 ]
[ 4 9] to [ 6 4 ]
7-segment display [A/B]
[ U 1 ] [ E28 ]
Function contents
Refrigerant circuit and control communication line check function (Cooling operation)
Refrigerant circuit and control communication line check function (Heating operation)
Indoor PMV forced full open function
Indoor remote controller discriminating function
Cooling test operation function
Heating test operation function
Indoor collective start/stop (ON/OFF) function
Outdoor refrigerant recovery operation function (Pump down function)
Error clear function
Solenoid valve forced open/close function
Fan forced operation function
Outside temp sensor manual adjustment function
Indoor No. 1 to 16 unit
Indoor No.17 to 32 unit
Indoor individual start/stop (ON/OFF) function
Indoor No.33 to 48 unit
Indoor No.49 to 64 unit
Function contents
Follower unit error / Corresponding unit fan operation function
SW01
1
7-segment display [B]
[ 10 ]
[ 15 ]
[ 20 ]
[ 25 ]
[ 30 ]
[ 35 ]
[ 40 ]
[ 43 ]
TO sensor value
10°C
15°C
20°C
25°C
30°C
35°C
40°C
43°C
SW01
1
7-segment display [B]
[ 45 ]
[ –15 ]
[ –10 ]
[ – 5 ]
[ 0 ]
[ 2 ]
[ 5 ]
[ 7 ]
TO sensor value
45°C
–15°C
–10°C
–5°C
0°C
2°C
5°C
7°C
SW02
1
2
3
4
5
6
7
8
SW02
9
10
11
12
13
14
15
16
8-7-10. Manual Adjustment Function of Outside Temp (TO) Sensor
This function is provided to fix TO sensor value manually by the switch operation on the interface P.C. board in
the outdoor unit. When the unit stops abnormally due to TO sensor failure, etc, an emergent operation is avail-
able by set up the value manually to position near the current outside temperature.
[Operation]
1. Set the rotary switches on the interface P.C. board to numbers as follows.
• SW01 [2] / SW02 [1] / SW03 [15]
• 7-segment display: [t o]