141
Check code
Main
remote
controller
H08
H14
H16
Outdoor 7-segment display
Check code
Sub-code
H08
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
H14
—
H16
01: TK1 oil circuit
system error
02: TK2 oil circuit
system error
03: TK3 oil circuit
system error
04: TK4 oil circuit
system error
AI-NET
central control
remote controller
d4
44
d7
Detected
position
I/F
I/F
I/F
Check code name
Oil level detective
temp sensor error
Compressor 2
case thermo
operation
Oil level detective
circuit system
error
MG-SW error
OCR operation
Status
All stop
All stop
All stop
All stop
All stop
All stop
Error detection condition
• Resistance value of
sensor is infinite or zero.
(Open/Short)
• Resistance value of
sensor is infinite or zero.
(Open/Short)
• Resistance value of
sensor is infinite or zero.
(Open/Short)
• Resistance value of
sensor is infinite or zero.
(Open/Short)
Compressor 2 case
thermostat operated.
Temperature change of
TK1 could not be detected
though compressor 1
started the operation.
Temperature change of
TK2 could not be detected
though compressor 2
started the operation.
Temperature change of
TK3 could not be detected
though compressor
started the operation.
Temperature change of
TK4 could not be detected
though compressor
started the operation, or
the difference from other
TK sensor changed for a
constant time only within
the specified range.
Check item (position)
• Check connection of TK1 sensor connector.
• Check characteristics of TK1 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check connection of TK2 sensor connector.
• Check characteristics of TK2 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check connection of TK3 sensor connector.
• Check characteristics of TK3 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check connection of TK4 sensor connector.
• Check characteristics of TK4 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check compressor 2 case thermo circuit. (Connector, cable, P.C. board)
• Check full opening of service valve. (Gas and liquid side)
• Check outdoor PMV clogging. (PMV1, 2)
• Check SV42 valve leak.
• Check miscabling/misinstallation of SV41 and SV42.
• Check valve opening of indoor PMV.
• Check 4-way valve error.
• Check refrigerant shortage.
• Check compressor error.
• Check TK1 sensor coming-off.
• Check characteristics of TK1 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check operation error of SV3E valve.
• Check capillary clogging of oil-equation circuit and operation error of stop valve.
• Check refrigerant stagnation in compressor.
• Check MG-SW or OCR.
• Check TK2 sensor coming-off.
• Check characteristics of TK2 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check SV3E valve operation.
• Check capillary clogging of oil equalization circuit and check stop valve operation.
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
• Check TK3 sensor coming-off.
• Check characteristics of TK3 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check SV3E valve operation.
• Check capillary clogging of oil-equalization circuit and check valve operation.
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
• Check TK4 sensor coming-off.
• Check characteristics of TK4 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check SV3E valve operation.
• Check capillary clogging of oil-equalization circuit and check valve operation.
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
MG-SW : Magnet Switch
OCR
: Over-current Relay