144
Check code
Main
remote
controller
P07
P10
P12
P13
P15
P17
P19
Outdoor 7-segment display
Check code
Sub-code
P07
01: Compressor
1 side
02: Compressor
2 side
P10
Indoor address
with trouble
—
—
P13
—
P15
01: TS condition
02: TD condition
P17
—
P19
Detected
outdoor unit No.
AI-NET
central control
remote controller
1C
Ob
11
47
AE
AE
bb
8
Detected
position
IPDU
I/F
Indoor
Indoor
I/F
I/F
I/F
I/F
I/F
Check code
name
Heat sink
overheat error
Indoor overflow
error
Indoor fan
motor error
Outdoor liquid
back detection
error
Gas leak
detection
(TS1 condition)
Gas leak
detection
(TD condition)
Discharge
temp TD2 error
4-way valve
operation error
Status
All stop
All stop
Corresponding
unit only stops.
All stop
All stop
All stop
All stop
All stop
Error detection condition
IGBT built-in temp sensor (TH) was overheated.
• Float switch operated.
• Float switch circuit disconnected or the
connector came off.
• The value of motor speed deviated from
target value was detected for certain time.
• Over-current protection operated.
<In cooling>
While the system is operating in COOL mode, a
high pressure value was detected in follower
unit in which compressor did not operate.
<In heating>
While the system is operating in HEAT mode,
outdoor PMV of which opening degree was
100p or less for a certain time.
Suction temp exceeded the judgment standard
temp for 10 minutes or more.
<TS error judgment standard temperature>
In cooling operation: 60°C or higher
In heating operation: 40°C or higher
Discharge temperature TD1 or TD2 was
continuously 108°C or higher for 10 minutes.
Discharge temperature (TD2) exceeded 115°C.
When abnormal refrigerating cycle data was
detected in heating
Check item (position)
• Check power voltage.
• Check outdoor fan system error.
• Check clogging of heat sink cooling duct.
• Check fixation between IGBT and heat sink.
(Check screwing and contact.)
• Check IPDU error.(IGBT built-in temp sensor (TH) error)
• Check the float switch connector.
• Check operation of drain pump unit.
• Check the drain pump circuit.
• Check clogging of drain pipe.
• Check indoor P.C. board error.
• Check connection of fan connector and wiring.
• Check fan motor error.
• Check indoor P.C. board error.
• Check influence of outside air control.
• Check indoor type code (DN=10) and the capacity code (DN=11).
• Check full close operation of outdoor PMV (1, 2).
• Check Pd and Ps sensor error.
• Check clogging of SV2 circuit.
• Check clogging of balance pipe.
• Check clogging of SV3B circuit.
• Check outdoor P.C. board (I/F) error.
• Check capillary clogging of oil return circuit from oil separator.
• Check leakage of check valve of the main discharge pipe.
• Check refrigerant shortage.
• Check full open of outdoor service valves (gas side, liquid side).
• Check outdoor PMV clogging (PMV1, 2).
• Check characteristics of TS1 sensor resistance value.
• Check 4-way valve error.
• Check leakage of SV4 circuit.
• Check refrigerant shortage.
• Check outdoor PMV clogging (PMV1, 2).
• Check characteristics of TD1, TD2 sensor resistance value.
• Check indoor air filter clogging.
• Check pipe clogging.
• Check SV4 circuit (Valve leakage, misinstallation)
• Check full opening of outdoor service valves
(gas side, liquid side).
• Check clogging of outdoor PMV (PMV1, 2).
• Check characteristics of TD2 sensor resistance value.
• Check 4-way valve error.
• Check leakage of SV42 circuit.
• Check SV4 circuit.
(Miscabling and misinstallation of SV41 and SV42)
• Error of 4-way valve error
• Check coil error and connector connection of 4-way valve.
• Check characteristics of TS1/TE1 sensor resistance value.
• Check characteristics of Pd, Ps pressure sensor output voltage.
• Check misconnection of TE1 and TL sensors.