227
10-2-1. Outdoor Interface P.C. Board
<Dip switch function exchange setup list>
* The outdoor unit connected with indoor/outdoor communication line becomes automatically the header unit.
The setup is unnecessary to be manually changed.
Part type
Exchange contents
Initial setup
at shipment
SW01 Rotary SW 4bit 16 step Display / Operation switch (1)
For 7-segment display / service operation
[1]
SW02 Rotary SW 4bit 16 step Display / Operation switch (2)
For 7-segment display / service operation
[1]
SW03 Rotary SW 4bit 16 step Display / Operation switch (3)
For 7-segment display / service operation
[1]
SW04 Push SW
For service [Operation/Start]
[Operation/Start] by pushing
—
SW05 Push SW
For service [Stop/End]
[Stop/End] by pushing
—
Bit 1 Backup setup
OFF
Bit 2
Bit 4
Bit 3
Bit 2
Bit 1
(Based on the following setup)
OFF
Bit 3
OFF
OFF
OFF
OFF
Normal
OFF
Bit 4
—
—
OFF
ON
No.1 COMP backup
OFF
—
—
ON
OFF
No.2 COMP backup
SW06 SW 4bit
—
—
ON
ON
Outdoor backup during cooling season
Bit 1 Demand control exchange
OFF: 0 – 100%, ON: Middle – 100%
OFF
Bit 2 Extended control demand function
(For 4-steps exchange)
OFF
Bit 3 For clean converter
OFF: Normal (unconnected), ON: Connected
OFF
SW07 SW 4bit
Bit 4
—
—
OFF
n
Header unit
Bit 1 Outdoor address setup exchange
OFF: Auto setup (Normal), ON: Manual setup
OFF
Bit 2 Judge indoor capacity over
OFF: YES (Normal), ON: NO
OFF
Bit 3 Correction of installed pipe size
OFF: Normal, ON: Size UP
(For outdoor expansion)
OFF
Bit 4 Judge abnormal No. of connected indoor units OFF: No error judgment, ON: Error
OFF
n
Follower unit
Bit 1
—
—
OFF
Bit 2
—
—
OFF
Bit 3
—
—
OFF
SW09 SW 4bit
Bit 4 Display of start priority No.
OFF: Outdoor unit No. [U.#] (#: 2 to 4)
ON : Outdoor start order No. [Y.#] (#: 2 to 4)
OFF
Bit 1
—
—
OFF
Bit 2 Outdoor fan high-static pressure operation
OFF : Normal, ON: High-static pressure operation
OFF
Bit 3
OFF: Normal,
ON : INV frequency upper limit restriction
OFF
SW10 SW 4bit
Bit 4
For low-noise operation
OFF: Normal, ON: Fan rpm upper limit restriction
OFF
Bit 1 Set up priority of cool/heat
(Based on following setup)
OFF
Bit 2
Bit 2
Bit 1
OFF
OFF
OFF
Priority on heating
OFF
ON
Priority on cooling
ON
OFF
Priority on No. of operating units
ON
ON
Priority on specific indoor unit
Bit 3
—
OFF
SW11 SW 4bit
Bit 4 Operation when indoor overflow detected
OFF: System stop,
ON : System operation continues
OFF
Bit 1
—
—
OFF
Bit 2
—
—
OFF
Bit 3
—
—
OFF
SW12 SW 4bit
Bit 4
—
—
OFF
Bit 1
—
—
OFF
Bit 2
—
—
OFF
Bit 3
—
—
OFF
SW13 SW 4bit
Bit 4 Line address setup
OFF
SW14 SW 4bit
Bit 1, 2, 3, 4
Line address setup
Refer to item “Address setup procedure”
OFF
Bit 1
OFF: No end terminal resistance, ON: Exists
ON
SW30 SW 2bit
Bit 2
End terminal resistance of communication
between outdoor units
OFF: No end terminal resistance, ON: Exists
ON
CN30 Check connector
Manual full opening setup of PMV
Opened: Normal, Short: Opened fully
Open
CN31 Check connector
Manual full closing setup of PMV
Opened: Normal, Short: Opened fully
Open
CN32 Check connector
Check for assembly line in factory.
Opened: Normal, Short: Check mode
Open