267
17-2-6. Comp-IPDU Board Replacement Procedure Manual
This service board is commonly installed in different models before shipment. If the board assembly is to be
replaced, replace it properly in accordance with the model, following this procedure manual.
<Replacement steps>
1. Turn off the power supply of the outdoor control unit (Turn off the power supply of the outdoor unit).
2. Confirm that the charged voltage of the condenser has been fully discharged. (Confirm that the voltage
between CN13 and CN15 is 0V).
3. Remove all of the connector and fasten and screw terminals connected to the A3-IPDU board (Remove the
connector and fasten terminals by holding them.)
4. Remove 2 screws that fix the IGBT (Q200) of the Comp-IPDU board to the heat sink.
5. Remove the Comp-IPDU board from the four card edge spacers.
6. Set the dip Switch (SW801) of the Comp-IPDU board, as instructed in the table below.
If the model is not specified, inspection “L29” is displayed and the equipment will not operate.
7. After setting the dip Switch of the service board, apply silicone grease evenly onto the IGBT and install it in
the outdoor control unit (Confirm that it is securely fixed to the card edge spacers).
8. Fix the IGBT of the Comp-IPDU board to the heat sink with two screws.
9. serted).
10. If a component part on the board is bent during board replacement, adjust it manually not to contact other
parts.
11. Install the cover then turn on the power supply. Check the operation.
Comp-IPDU No.
JAt shipment
No.1
No.2
SW801
Bit 1
Bit 2
ON
ON
ON
ON
ON
OFF
Noise
filter
board
Terminal
Power
supply
P.C. board
assembly
Interface board
Board layout the inverte
Comp-IPDU
No.1
Comp-IPDU
No.2
Magnetic
switch
Fan IPDU
Switch layout on the board
Q200
IC101
IC222
SW801
T01
T03
CN26
T05
CN15
CN13
CN17
T04
T02
Содержание MMC-AP0151H
Страница 270: ......