Chapter 4 Settings
6F8C1686
38
4.1
Switches setting
4.1.1
DeviceNet communication speed and node address setting switch
Figure 4-1 DeviceNet communication speed and node address setting switch
Set the communication speed of DeviceNet with switches 1 and 2, and set the node address of DN611B
using switches 3 to 8. The following table shows the settings.
Table 4-1 DeviceNet communication speed and node address settings
S1
S2
Communication speed
OFF
OFF
125 kbps
OFF
ON
250 kbps
ON
OFF
500 kbps
ON
ON
Unavailable
S3
S4
S5
S6
S7
S8
Node address
OFF
OFF
OFF
OFF
OFF
OFF
0
OFF
OFF
OFF
OFF
OFF
ON
1
OFF
OFF
OFF
OFF
ON
OFF
2
OFF
OFF
OFF
OFF
ON
ON
3
…
…
…
…
…
…
…
ON
ON
ON
ON
OFF
OFF
60
ON
ON
ON
ON
OFF
ON
61
ON
ON
ON
ON
ON
OFF
62
ON
ON
ON
ON
ON
ON
63
Note
The switches on the entire module take in the values when the power is turned on. After changing the switch, turn on
the power again.
Important
Operate the DIP switch using a precision screwdriver.
Содержание DeviceNet nv Series
Страница 1: ...Unified Controller nv Series type1 light DeviceNetTM Module DN611B Instruction Manual 6F8C1686 ...
Страница 30: ...Chapter 1 DN611B Introduction 6F8C1686 14 ...
Страница 92: ...Chapter 4 Settings 6F8C1686 76 3 Register the slave node Figure 4 16 Register the slave node Drag and Drop ...
Страница 149: ...13 3 133 B Appendix B Outside Dimension ...
Страница 150: ...Appendix B Outside Dimension 6F8C1686 134 Figure B 1 External dimension 135 mm 35mm 130 mm 111 5mm 105mm ...
Страница 151: ...13 5 135 C Appendix C Related products C 1 Network components 136 C 2 DeviceNet setting tool 138 ...