■DeviceNet communication speed and node address setting switch (BAUD / MAC)
Set the data rate of DeviceNet (Baud rate) and the node address of DN611B. Refer to Chapter 4 for the
setting.
Table 2-2 DeviceNet communication speed and node address setting switch
S1
S2
Baud rate
OFF
OFF
125kbps
OFF
ON
250kbps
ON
OFF
500kbps
ON
ON
(reserved)
S3
S4
S5
S6
S7
S8
Node Address
OFF
OFF
OFF
OFF
OFF
OFF
0
OFF
OFF
OFF
OFF
OFF
ON
1
OFF
OFF
OFF
OFF
ON
OFF
2
OFF
OFF
OFF
OFF
ON
ON
3
ON
ON
ON
ON
OFF
OFF
60
ON
ON
ON
ON
OFF
ON
61
ON
ON
ON
ON
ON
OFF
62
ON
ON
ON
ON
ON
ON
63
■DeviceNet communication connector
Connect the DeviceNet communication cable. See Chapter 3 for wiring.
■Operation mode setting switch
Table 2-3 Operation mode setting switch
No.
Name
Note
M1
Reserve
OFF
M2
Reserve
OFF
M3
Reserve
OFF
M4
Reserve
OFF
Turn off all 4-bit operation mode setting switches before use.
Before turning on the module, make sure all switches are OFF.
The DIP-Switch 2 : BUSOFF for DN611/DN611A is not supported.
The specifications of the HMS board for DN611B are different from those for DN611 / DN611A.
The DN611B cannot resume transmission after busoff. so DN611B requires a system reboot after busoff
recovery.
Содержание DeviceNet nv Series
Страница 1: ...Unified Controller nv Series type1 light DeviceNetTM Module DN611B Instruction Manual 6F8C1686 ...
Страница 30: ...Chapter 1 DN611B Introduction 6F8C1686 14 ...
Страница 92: ...Chapter 4 Settings 6F8C1686 76 3 Register the slave node Figure 4 16 Register the slave node Drag and Drop ...
Страница 149: ...13 3 133 B Appendix B Outside Dimension ...
Страница 150: ...Appendix B Outside Dimension 6F8C1686 134 Figure B 1 External dimension 135 mm 35mm 130 mm 111 5mm 105mm ...
Страница 151: ...13 5 135 C Appendix C Related products C 1 Network components 136 C 2 DeviceNet setting tool 138 ...
Страница 159: ...1686 2 2201 ...