Chapter 6 Troubleshooting
6F8C1686
120
6.2.3
No Run Mode
The explanations in this section are based on the assumption that the module has started normally. To
change the mode from standby to run after starting the module, it is necessary to set the local node parameters
by a parameter setting request before issuing an operation mode control request. Also, clear the scan list
before setting slave device parameters by a parameter setting request if the configuration of the slave devices
is changed.
1) Local node parameter setting request
Figure 6-5 Local Node Parameter Setting Request Check Item
2) Operation Mode Control Request
Figure 6-6 Operation Mode Control Request Check Items
START
Is the parameter setting
request executed?
Parameter setting request?
Remove the cause of trouble
based on completion status.
END
Yes
Yes
Execute the local node parameter
setting request
See how to use semaphore area.
No
No
If the network has been set by the HMS setting tool,
go to the operation mode control request.
START
Is the operation mode
control request executed?
Is the operation mode
control request completed?
Remove the cause of trouble
based on completion status.
END
Yes
Execute the operation mode
control request.
See how to use semaphore area
No
No
Yes
Содержание DeviceNet nv Series
Страница 1: ...Unified Controller nv Series type1 light DeviceNetTM Module DN611B Instruction Manual 6F8C1686 ...
Страница 30: ...Chapter 1 DN611B Introduction 6F8C1686 14 ...
Страница 92: ...Chapter 4 Settings 6F8C1686 76 3 Register the slave node Figure 4 16 Register the slave node Drag and Drop ...
Страница 149: ...13 3 133 B Appendix B Outside Dimension ...
Страница 150: ...Appendix B Outside Dimension 6F8C1686 134 Figure B 1 External dimension 135 mm 35mm 130 mm 111 5mm 105mm ...
Страница 151: ...13 5 135 C Appendix C Related products C 1 Network components 136 C 2 DeviceNet setting tool 138 ...
Страница 159: ...1686 2 2201 ...