6.1 RAS
Unified Controller nv Series DeviceNet Module DN611B Instruction Manual
117
Table 6-23 Node Status Detail
Code
Status
0
Device OK or Not in Scan List
70
DN611B detects an error in duplicate node address check.
72
DN611B cannot communicate with slave devices.
73
Vendor ID, product type, and product code of a slave device differ
from those on the DN611B scan list.
75
No slave device exists on the network. No slave device is
registered on the scan list.
76
DN611B has detected communication timeout due to no response
from slave devices.
77
Slave device transmission size differs from that on the DN611B
scan list.
78
DN611B unable to start transmission to slave devices.
79
DN611B unable to send to slave devices.
80
DN611B's communication port is in idle mode.
81
DN611B's communication port is in fault mode.
82
Send/receive data fragment error
83
Slave device initialization refused.
84
Slave device initialization not completed.
85
DN611B receive buffer overflow
91
DN611B busoff
92
DN611B network power error
In DN611B, the module status code and node status code differ depending on the boot order.
If the slave device is started first and then DN611B, module status code is 01H / node status is 84H.
If DN611B is started first and then the slave device, module status code is 00H / node status is 00H
This is based on the node status specifications of the HMS board.
The module status code is determined based on the node status. Therefore, node status 84H is determined
to be module status code 01H.
To set the module status code 00H / node status 00H, first start DN611B and then the slave, or turn the
network power off and then on again after starting all the modules.
Содержание DeviceNet nv Series
Страница 1: ...Unified Controller nv Series type1 light DeviceNetTM Module DN611B Instruction Manual 6F8C1686 ...
Страница 30: ...Chapter 1 DN611B Introduction 6F8C1686 14 ...
Страница 92: ...Chapter 4 Settings 6F8C1686 76 3 Register the slave node Figure 4 16 Register the slave node Drag and Drop ...
Страница 149: ...13 3 133 B Appendix B Outside Dimension ...
Страница 150: ...Appendix B Outside Dimension 6F8C1686 134 Figure B 1 External dimension 135 mm 35mm 130 mm 111 5mm 105mm ...
Страница 151: ...13 5 135 C Appendix C Related products C 1 Network components 136 C 2 DeviceNet setting tool 138 ...
Страница 159: ...1686 2 2201 ...