2.2 Functions of parts
Unified Controller nv Series DeviceNet Module DN611B Instruction Manual
17
2.2
Functions of parts
■status display LED
Table 2-1 Status display LED
Name
State
Meaning
NS
(Network Status)
Off
Not powered, not on line
Green
On line, one or more connections established
Green, flashing
On line, no connections established
Red
Critical link failure
Red, flashing
One or more connections timed out
Alternating Red / Green Device self-test in progress
MS
(Module Status)
Off
No power
Green
Normal operation
Red
Major fault
Red, flashing
Minor fault
Alternating Red / Green Device self-test in progress
SM
(Scanner Mode)
Off
No power
Green
Run mode
Green, flashing
Idle mode
SP
Off
No use
Important
Other than the above, DeviceNet module errors such as H/W initialization errors cannot be determined from the LEDs.
If a problem occurs, please refer to "6.1 RAS" to obtain the event history.
■Configurator / Tool connection connector (TOOL)
Configurator / Tool connection connector is to connect the DeviceNet setting tool manufactured by HMS
(ACM) and set the slave I/O of DeviceNet. For details, refer to "Chapter 4."
Содержание DeviceNet nv Series
Страница 1: ...Unified Controller nv Series type1 light DeviceNetTM Module DN611B Instruction Manual 6F8C1686 ...
Страница 30: ...Chapter 1 DN611B Introduction 6F8C1686 14 ...
Страница 92: ...Chapter 4 Settings 6F8C1686 76 3 Register the slave node Figure 4 16 Register the slave node Drag and Drop ...
Страница 149: ...13 3 133 B Appendix B Outside Dimension ...
Страница 150: ...Appendix B Outside Dimension 6F8C1686 134 Figure B 1 External dimension 135 mm 35mm 130 mm 111 5mm 105mm ...
Страница 151: ...13 5 135 C Appendix C Related products C 1 Network components 136 C 2 DeviceNet setting tool 138 ...
Страница 159: ...1686 2 2201 ...