D.1 List of differences between DN611A and DN611B
Unified Controller nv Series DeviceNet Module DN611B Instruction Manual
141
item
Difference in DN611B
Reference
Module status code
Node status
-In DN611A, after normal startup, the module status code of
the local node will be "00H: normal status" and the node
status will be "00H: normal status".
-In DN611B, the module status code and node status code
differ depending on the boot order.
If the slave device is started first and then DN611B, module
status code is 01H / node status is 84H.
If DN611B is started first and then the slave device, module
status code is 00H / node status is 00H
This is based on the node status specifications of the HMS
board.
The module status code is determined based on the node
status. Therefore, node status 84H is determined to be
module status code 01H.
To set the module status code 00H / node status 00H, first
start DN611B and then the slave, or turn the network power
off and then on again after starting all the modules.
Chapter
6.1.3
Содержание DeviceNet nv Series
Страница 1: ...Unified Controller nv Series type1 light DeviceNetTM Module DN611B Instruction Manual 6F8C1686 ...
Страница 30: ...Chapter 1 DN611B Introduction 6F8C1686 14 ...
Страница 92: ...Chapter 4 Settings 6F8C1686 76 3 Register the slave node Figure 4 16 Register the slave node Drag and Drop ...
Страница 149: ...13 3 133 B Appendix B Outside Dimension ...
Страница 150: ...Appendix B Outside Dimension 6F8C1686 134 Figure B 1 External dimension 135 mm 35mm 130 mm 111 5mm 105mm ...
Страница 151: ...13 5 135 C Appendix C Related products C 1 Network components 136 C 2 DeviceNet setting tool 138 ...
Страница 159: ...1686 2 2201 ...